The TSRD is our standard product for switching on three-phase transformers of any design, for example for isolation transformers in special vehicles with rated currents of up to 50 A. For the operation of the TSRD, an external bypass contactor is required to bridge the internal actuators.
It also features soft-on, allowing three-phase transformers or three single-phase transformers together to be switched on at no-load or under load without an inrush surge. The inrush current surge is also avoided here and not just limited.
Mains Voltage |
200, 400, 500 VAC and various wide voltage ranges as per request |
Frequency |
45 - 65 Hz |
Rated Current |
32 A & 50 A (Option) |
Max. Peak Current: |
For 32 A (Rated Current) |
|
400 A (tpeak = 10 ms) |
|
Leakage current in blocked condition :12 mA at 400 V |
|
Load integral limit: 800 A2s (t = 10 ms) |
Operating Temp |
(-)15 °C - 50 °C |
Control Input 1 & 2 |
Across an opto coupler in TSRD, seperate potential Driver A1-A2 bzw. A4-A5 U= 16 – 121 VAC/DC I= 1 - 8,3 mA Driver A1-A3 bzw. A4-A6 U= 93 – 550 VAC I= 1,3 - 8,1 mA |
Construction |
Encapsulated, housing made from insulating material |
Housing |
Material PVC and Polyamide, Flammability class UL94 V0 |
Degree of protection |
In the housing: IP20 |
EMC (CE) |
Interference immunity: EN 61000-6-2; Interference emission : EN 61000-6-3 |